EATON PFIM-40/2/03-MW 2Pole Residual current circuit breaker (RCCB)Technical Details Datasheet Residual current circuit breaker (RCCB), 40A, 2p, 300mA, type AC Residual current circuit breaker PFIM, 2 pole, Rated current In: 40 A, Rated short circuit strength Icn: 10 kA, Rated fault current IN: 0. 3 A, Type AC, AC current sensitive, Partly surge proof 250 A, Switchgear for residential and commercial applications Delivery program Basic function Residual current circuit breakers Number of poles 2 pole Application
Shopping security
Each payment you make on thelockerguy is secured with strict SSL encryption and PCI DSS data protection protocols
Residual current circuit breaker (RCCB), 40A, 2p, 300mA, type AC
Residual current circuit-breaker PFIM, 2 pole, Rated current In: 40 A, Rated short-circuit strength Icn: 10 kA, Rated fault current IΔN: 0.3 A, Type AC, AC current sensitive, Partly surge-proof 250 A, Switchgear for residential and commercial applications
Delivery program
Basic function
Residual current circuit-breakers
Number of poles
2 pole
Application
Residual current circuit-breaker for residential and commercial applications
Rated current [In]
40 A
Rated short-circuit strength [Icn]
10 kA
Rated fault current [IΔN]
0.3 A
Type
Type AC
Tripping
non-delayed s…
Product range
PFIM
Sensitivity
AC current sensitive
Impulse withstand current
Partly surge-proof 250 A
Technical data
Electrical
Standards
IEC/EN 61008
Rated operational voltage [Ue][Ue]Rated operating voltage [Ue]
230 V AC
Rated frequency [f]
50 Hz
Limit values of the operating voltageTest circuit
196 - 264 V AC
Sensitivity
AC current sensitive
Rated insulation voltage [Ui]
440 V
Rated impulse withstand voltage [Uimp]
4 kV
Rated short-circuit strength [Icn]
10 kA
Rated making and breaking capacity / Rated residual making and breaking capacity [Im/ IΔm]
500 A
lifespanElectrical [Operations]
≧ 4000
lifespanMechanical [Operations]
≧ 20000
References
Auxiliary switch for subsequent installation
Z-HK 248432
Tripping signal contact for subsequent installation
Z-NHK 248434
Remote control and automatic switching device
Z-FW/LP 248296
Compact enclosure
KLV-TC-2 276240
Sealing cover set
Z-RC/AK-2MU 285385
Mechanical
Standard front dimension
45 mm
Device height
80 mm
Built-in width
35 (2TE) mm
Mounting
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Degree of Protection
IP20, IP40 with a suitable enclosure
Terminals top and bottom
Open mouthed/lift terminals
Terminal protection
DGUV VS3, EN 50274
Terminal cross-sectionSolid
1.5 - 35 mm2
Terminal cross-sectionStranded
2 x 16 mm2
Thickness of busbar material
0.8 - 2 mm
Permissible storage and transport temperatures
-35 - +60 °C
Climatic proofing
25-55°C/90-95% relative humidity according to IEC 60068-2
Thickness of busbar materialMaterial thickness
0.8 - 2 mm
Show More
EATON PFIM-40/2/03-MW 2Pole Residual current circuit breaker (RCCB)